Bộ nguồn UNO-PS/1AC/24DC/ 30W

Thông số kỹ thuật bộ nguồn Phoenix contact UNO-PS/1AC/24DC/ 30W

Orderkey Phoenix 2902991
Packing unit 1 pc
Catalog page Page 226 (C-4-2017)
GTIN 4046356729192
Weight per Piece (excluding packing) 180.000 g
Custom tariff number 85044030
Country of origin PL (Poland)

Dimensions

Width 22.5 mm
Height 90 mm
Depth 84 mm

đại lý UNO-PS/1AC/24DC/ 30W

Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2

 

Input data

Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC
Current consumption 0.8 A (100 V AC)
0.4 A (240 V AC)
Nominal power consumption 72.1 VA
Inrush surge current < 20 A (typical)
Mains buffering typ. 25 ms (120 V AC)
typ. 115 ms (230 V AC)
Input fuse 2 A (slow-blow, internal)
Choice of suitable circuit breakers 6 A … 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.47
Type of protection Transient surge protection
Protective circuit/component Varistor

Output data

Nominal output voltage 24 V DC ±1 %
Nominal output current (IN) 1.25 A (-25 °C … 55 °C)
Derating 55 °C … 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance < 35 V DC
Protection against surge voltage on the output ≤ 35 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (Dynamic load change 10 % … 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 60 mVPP (with nominal values)
Output power 30 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 0.3 W
Power loss nominal load max. < 5 W

 

Net weight 0.15 kg
Efficiency typ. 87 % (120 V AC)
typ. 88 % (230 V AC)
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
Protection class II (in closed control cabinet)
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1158000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: 0 mm horizontally, 30 mm vertically

 

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m
Frequency range 1.4 GHz … 2 GHz
Test field strength 3 V/m
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 10 kHz … 80 MHz
Voltage 10 V (Test Level 3)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Safety of transformers EN 61558-2-16
Standard – Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard – Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
NEC Class 2 as per UL 1310
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz … 150 Hz, 2.3g, 90 min.
Approval – requirement of the semiconductor industry with regard to mains voltage dips EN 61000-4-11
Information technology equipment – safety (CB scheme) CB Scheme

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration”
eCl@ss 4.0 27040702
eCl@ss 4.1 27040702
eCl@ss 5.0 27049002
eCl@ss 5.1 27049000
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002
eCl@ss 8.0 27049002
eCl@ss 9.0 27040701

ETIM

ETIM 3.0 EC001039
ETIM 4.0 EC000599
ETIM 5.0 EC002540
ETIM 6.0 EC002540

UNSPSC

UNSPSC 6.01 30211502
UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121004

Trả lời